Application Note
Issue Date September 8, 2008
© 2008 BASO Gas Products 1
Part No. BASO-AN-PB/THERMOCOUPLES, Rev.- www.baso.com
This document is intended to aid the appliance engineer or authorized
service contractor in making a standing pilot application. Pilot burners are
manufactured with a variety of tips and mounting configurations.
Representative types of mounting with standard pilots are illustrated in
Figure 1. Dimensions shown are approximate and may vary, provided the
requirements of good ignition are met. See Good Practice Rules.
The following are good practice rules for governing the location of the
pilot:
Locate the pilot so that it can be reached easily for lighting.
Locate the pilot in a position that has a fixed relation to the main
burner (see Figure 1).
Pilot Ignition Port 3/8" Above
and 1/4" Away (Or Closer)
from Center of Nearest Main
Burner Port
Mounting Position Examples for Pilot Burners
pilot
Figure 1: Pilot Location
Locate the pilot burner in a position that will receive incoming air and
not products of combustion from the main burner. The pilot should
be located where it will not be affected by an excessive draft of
incoming air.
Locate the pilot burner in such a position that it does not receive the
full force of igniting or extinguishing puffs from the main burner.
Locate the pilot burner in a position that will allow ready removal for
cleaning.
Pilot Burners/Thermocouples
Application
Good Practice
Rules
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - Pilot Burners/Thermocouples

Application Note Issue Date September 8, 2008 © 2008 BASO Gas Products 1 Part No. BASO-AN-PB/THERMOCOUPLES, Rev.- www.baso.com This d

Page 2

2 Pilot Burners/Thermocouples Technical Bulletin When the pilot burner has been installed, carefully make the following observations and tests: 1

Page 3 - Turn Down Test

Pilot Burners/Thermocouples Technical Bulletin 3 Table 1: Thermocouple Output Table Thermocouple Lead Series Number Code Number Turn Dow

Page 4 - Instruments

4 Pilot Burners/Thermocouples Technical Bulletin 2. Reduce the flame on the pilot through the use of the “B” valve to the point where the open c

Page 5 - PO Box 170

Pilot Burners/Thermocouples Technical Bulletin 5 5. If you cannot secure ignition of the main burner when the pilot flame has been reduced to t